Ecosoft Industrial RO System 12 to 48 m3/h
Industrial RO Systems
⚠️ Custom product — Right of withdrawal does not apply
This product is custom-built or configured to your specifications. Under Article L221-28 of the French Consumer Code, the right of withdrawal does not apply to goods made to the consumer’s specifications or clearly personalized.
Before placing your order, please make sure this product meets your needs. Our team is available to advise you at 03 66 88 17 85.
Ecosoft high-flow industrial RO systems
Need a high flow rate of purified water? Choose an Ecosoft industrial RO system.
Reliable and efficient, these systems are designed for factories and facilities that require large volumes of purified water. The range is available in capacities of 12 m³/h, 16 m³/h, 24 m³/h, 36 m³/h and 48 m³/h.
All models feature Grundfos pumps, designed to deliver high pumping capacity with good energy efficiency.
Allowable TDS: the 24, 36 and 48 m³/h versions can treat water with up to 3,000 mg/L, while the 12 and 16 m³/h versions accept up to 4,500 mg/L.
Equipment
Configuration by production flow rate
12 m³/h version
12 m³/h industrial RO system
- Grundfos CR 36-6 high-pressure pump
- 4 8040 membrane housings holding 4 membranes each
- Stainless steel housing with 7 PP filters, 2.5 × 40"
- 2 motorized valves
- 2 balancing valves
- Electrical cabinet with Ecosoft controller
- Piping and instrumentation
- Steel frame
16 m³/h version
16 m³/h industrial RO system
- Grundfos CR 20-10 high-pressure pump
- 4 8040 membrane housings holding 4 membranes each
- Stainless steel housings with 7 PP filters, 2.5 × 40"
- 2 motorized butterfly valves
- 2 balancing valves
- Electrical cabinet with Ecosoft controller
- Piping and instrumentation
- Steel frame
24 m³/h version
24 m³/h industrial RO system
- Grundfos CR 45-4 high-pressure pump
- 6 8040 membrane housings holding 4 membranes each
- 2 stainless steel housings with 7 PP filters, 2.5 × 40"
- 2 motorized butterfly valves
- 2 balancing valves
- Electrical cabinet with Ecosoft controller
- Piping and instrumentation
- Steel frame
36 m³/h version
36 m³/h industrial RO system
- Grundfos CR 45-4-2 high-pressure pump
- 6 8040 membrane housings holding 6 membranes each
- Stainless steel housing with 7 PP filters, 2.5 × 40"
- 2 motorized butterfly valves
- 2 balancing valves
- Electrical cabinet with Ecosoft controller
- Piping and instrumentation
- Steel frame
48 m³/h version
48 m³/h industrial RO system
- Grundfos CR 64-4 high-pressure pump
- 8 8040 membrane housings holding 6 membranes each
- 2 stainless steel housings with 7 PP filters, 2.5 × 40"
- 2 motorized butterfly valves
- 2 balancing valves
- Electrical cabinet with Ecosoft controller
- Piping and instrumentation
- Steel frame
Membrane selection
Several configurations available
XLE-440
ELP-8040
On request
External sourcing available
Please note: for the classic version, the software used to configure and operate the RO system is available only in English and Russian, and not in French.
Acceptable water quality
Recommended feed water conditions
| Parameter | Allowable value |
| TDS – 12 and 16 m³/h | ≤ 4,500 mg/L |
| TDS – 24, 36 and 48 m³/h | ≤ 3,000 mg/L |
| Residual chlorine | < 0.1 mg/L |
| Hardness | < 3 meq/L (150 mg/L CaCO₃ or 15 °f) |
| Iron | < 0.1 mg/L |
| Manganese | < 0.05 mg/L |
| Silicate | < 20 mg/L |
| Chemical oxygen demand | < 4.0 mg/L O₂ |
| Hydrogen sulfide | None |
| SDI | 5 |
Chlorine present: if your water contains more free chlorine, add an activated carbon system upstream of the RO system.
Water too hard: if hardness exceeds the recommended value, or to improve membrane efficiency and service life, add a water softener upstream of the installation.
Technical diagrams
12 to 48 m³/h configurations
Technical diagram – 12 m³/h

Technical diagram – 16 m³/h

Technical diagram – 24 m³/h

Technical diagram – 36 m³/h

Technical diagram – 48 m³/h

Documents
Documents and downloads
Industrial RO system assembly documentation
Assembly guide
Review the main assembly and connection instructions for your industrial RO system.
Download the assembly guideSpecifications
Technical specifications
Comparison of 12 to 48 m³/h versions
| Specifications | 12 m³/h | 16 m³/h | 24 m³/h | 36 m³/h | 48 m³/h |
|---|---|---|---|---|---|
| Gross weight | 1,100 kg | 1,200 kg | 1,500 kg | 1,700 kg | — |
| Net weight | 820 kg | 900 kg | 1,100 kg | 2,200 kg | 1,900 kg |
| System dimensions ± 5 % |
400 × 140 × H 210 cm | 550 × 160 × H 240 cm | 550 × 160 × H 240 cm | 700 × 240 × H 250 cm | 700 × 250 × H 240 cm |
| Crate dimensions | — | — | — | — | — |
| Filtration capacity * | 12 to 15 m³/h 3,200 to 4,000 GPH |
16 to 20 m³/h 4,200 to 5,300 GPH |
24 to 28 m³/h 6,400 to 7,400 GPH |
36 to 42 m³/h 9,500 to 11,100 GPH |
48 m³/h |
| Recovery rate ** | 75 % 1 liter of wastewater for every 3 liters produced |
||||
| Maximum TDS | 4,500 mg/L | 4,500 mg/L | 3,000 mg/L | 3,000 mg/L | 3,000 mg/L |
| Inlet flow rate | 16 to 20 m³/h during operation | 20 to 25 m³/h during operation | 30 to 40 m³/h during operation | 50 to 60 m³/h during operation | 65 to 80 m³/h during operation |
| Operating pressure | 8 to 12 bars | ||||
| Maximum pressure | 14 bars | 14 bars | 14 bars | 14 bars | 14 bars |
| Power supply | 380 to 400 V / 50 Hz | ||||
| Electrical power | 11 kW | 11 kW | 18.5 kW | 22 kW | 22 kW |
| Pre-filter micron rating | 5 µm | ||||
Scroll the table horizontally on your mobile device to view all specifications.
Close-up of the central section of the industrial RO system
Connections
Water connection diameters
| Connection | 12 m³/h model | 16 and 24 m³/h models | 36 and 48 m³/h models |
|---|---|---|---|
| Inlet | DN65 (flange) | DN80 (flange) | DN100 (flange) |
| Purified water outlet | DN50 (flange) | DN65 (flange) | DN80 (flange) |
| Wastewater outlet | DN65 (flange) | DN80 (flange) | DN100 (flange) |